ASSIGNMENT-4
UNIT-3: Transformers
1.(A) Explain the working principle of 1-Ø (Single phase) Transformer
and what happens If DC supply is given to transformer? Give the applications of
transformer.
(B) Derive the induced emf equation of transformer
(C) The maximum flux density in the core of
250/3000V, 50Hz, single phase transformer is 1.2 web/m2 .if the
emf/turn is 8v determine the primary and secondary turns and the area of the core.
[Ans: 32, 375, 0.02m2]
2. (A) Explain the losses that occur in
Transformers
(B)Derive the maximum efficiency condition
and expression for load KVA corresponding to Maximum efficiency
(c).A 3000/300V 1-phase
transformer gives 0.6A and 60W as ammeter and wattmeter reading, when supply is
given to the low voltage winding, the high voltage winding is kept open. Find (i)
power factor of no load current (ii) Magnetizing current (iii) Iron loss
component
[Ans: 0.333 lagging,
0, 05656A, 0.02A]
3. (A) Draw
the phasor diagram of Transformer under no load.(IDEAL T/F AND PRACTICAL T/F)
(B) Draw the phasor diagram of transformer on load (consider
resistance and leakage reactance)
( c ). A 250 KVA single phase
transformer has iron loss of 1.8KW.The full load copper loss is
2000watts.caluculate (i) Efficiency at full load. (ii) KVA supplied at maximum efficiency.(iii)Maximum
efficiency at 0.8 lagging power factor.
[Ans:98.135%,237.1708KVA,98.137%]
4. (A)
Define efficiency and regulation of a Transformer. Explain how will you pre -
determine the efficiency and regulation with neat circuit diagrams.
(OR)
Explain OC
and SC tests on single phase transformer to determine regulation and efficiency
(B) Explain why the transformer is rated in KVA
instead of KW.
( C) a 200/400V, 50 Hz 1-phase transformer has
the following test data.
OC Test (LV):200V,
0.7A, 70w on LV side.
SC Test (Hv); 15V,
10A, 80W on HV side.
Calculate the
secondary voltage when delivering 5KW at 0.8 lag v1=200v.
5. (A) Explain the construction of transformer.
( B) The required no load
voltage ratio in a 150 KVA, 50Hz single phase transformer is 5000/250V.find the
efficiency at half rated KVA, Unity power factor and also efficiency at full
load 0.8 PF lagging if the full load copper losses are 1800watt, core losses
are 1500W.
[Ans:97.46%,97.33%]